FGW10-15

FGW10-15 Isolating switch

The disconnect switch / isolating switch with manual operation mechanism is used for sectionalizing or isolating circuits on outdoor distribution overhead systems up to 38KV.

Characteristic:

Voltage: 12 / 36kV

Current: 400 / 630A

Application: Overhead Distribution Line

Standard: IEC 62271-102

Request A Quote
Main features

Technical parameter.

Electrical characteristics Specification Unit
Rated voltage of Disconnector 12 36 kV
Rated current 400 / 630 A
Rated frequency 50 Hz
Lighting Impulse withstand voltage 95 170 kV
Power frequency withstand voltage in 1 min (Dry) 42 70 kV
Power frequency withstand voltage in 10 s  (Wet) 36 60 kV
Rated short circuit withstand current 16 kA
Rated short circuit withstand time 3 s
Rated peak withstand current 40 kA
Creepage 25 mm/kV
Blade stopped degree in opening position 160 Degree
       
Spare parts      
Mounting bracket with/without  
Terminal clamp with/without  
Loadbuster Hook with/without  
Self locking Mechanism with  
       
Material      
Terminal pads Brass/Copper plated by silver  
Blade Copper plated by siliver  
Insulator Porcelain / Polymer  
Channel Base Steel hot galvanized  
Operating eye Stainlesss steel / Brass  
       
Package      
Qty/package 1 pc/carton
     
Service conditions    
Environment maximum temperature 40 °C
Pollution level Heavy  
Altitude ≤1000 Meter
     
Standard IEC 62271-102:2001  
Return list
Get in Touch

GET A QUOTE

GET IN TOUCH NOW
Captcha Code
×